6 DXi-Series Specifications
DXi3500 and DXi5500 Site Planning Guide
Performance
Characteristics 0
Table 3 lists the performance characteristics of the DXi-Series system.
Table 3 Performance
Characteristics
Environmental
Specifications 0
Table 4 provides various DXi-Series environmental specifications.
Table 4 Environmental
Specifications
Interface
Hardware 10/100/1000-BaseT Ethernet (2 ports)
Optional Fibre Channel interface (2 ports for DXi3500 and 4 ports
for DXi5500)
Average
Swap Time
2 seconds, consisting of two Move Medium commands
Inventory
Less than 10 seconds, fully loaded with labeled car-
tridges
Power Environment
Electrical inputs Voltage 100 VAC to 240 VAC (DXi3500)
110 VAC to 240 VAC (DXi5500)
Rated Frequency 50 to 60 Hz
Rated Current
(DXi3500)
550 watts
5.5A @ 110VAC - across 2N redun-
dant power cords*
2.75A @ 200VAC - across 2N redun-
dant power cords*
Rated Current
(DXi5500)
900 watts
9A @ 110VAC - across N+1 redun-
dant power cords**
4.5A @ 200VAC - across N+1 redun-
dant power cords**
Maximum Circuit
Required
DXi3500 at 110VAC - 5.5A circuit
DXi3500 at 200VAC - 2.75A circuit
DXi5500 at 110VAC - 9A circuit
DXi5500 at 200VAC - 4.5A circuit
* 2N power redundancy - the system can sustain a 50% power supply loss.
** N+1 power redundancy - the system can sustain a single power supply loss.