Chapter 6 Maintaining Your Library
Maintenance Actions
Scalar i6000 User’s Guide 444
Horizontal Alignments 6
The horizontal alignments graphical report shows the results for tests of
horizontal alignment of tape magazines on the drive-side and door-side
across frames, and for horizontal alignment of I/E stations across frames.
This graphical report is not generated for libraries
with only one frame.
If the graphical report shows a failed result for the drive-side or door-
side, make sure that all tape magazines are installed properly on that
side and that the calibration targets are correctly snapped on to the
magazines.
If the graphical report shows a failed result
for the I/E station, make
sure the I/E station and front door are completely shut.
If running the test again still generates
failed results, realign the
middle X-axis rail and check the alignment of the top and bottom X-
axis rails at the location of the failure.
See figure
42 on page 445.