Service Menu 4-127
September 2007
Move Dialog
Path: Main Menu Service Diags Accessor Move
Use the Move dialog to move the accessor in a figure eight
pattern without accessing cartridges. See Figure 4-190.
Figure 4-190 Move Dialog
Parameters Description
Cycles to Run Indicates the desired cycle
count (001–999)
Accept Y to accept changes
N to reject changes
If Y is selected, the Response Screen appears. See
Figure 4-191 on page 4-127. Otherwise, the changed
parameters continue to display but no action is taken.
Figure 4-191 Response Dialog
Parameters Description
Cancel Y to cancel the test.
N to continue running the test.
Cycle Displays the number of
completed test cycles of the
requested cycles
Status Displays the status of the
selected cycle (Running,
completed, Error, Cancelled)
Cancel Y to cancel the test.
N to continue running the test.
If Y is selected for the Cancel parameter value, the test is
canceled. Otherwise, the test continues.
The accessor test
does corner moves.
Cycles to run:009<
Accept: N
DIAGS ACCESSOR TEST
Cycle :006 of 009
Status:Running
Cancel: N<
Note
If the operation
stops, the Cancel
parameter no
longer displays.