Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping
Quantum Scalar i40 and Scalar i80 User’s Guide 295
b Install four thumbscrews into the floor of the library in the
locations shown in
Figure 73 on page 295. They will screw
through the Y-tray and hold it in place on the floor of the
li
brary.
Figure 73 Restraining the Y-
tray
Four Y-tray restraint
thumbscrews
Rack “ear” overhangs
edge of desk or table
c Do NOT turn the library back to an upright position at this
point. Leave it on its side until you place it in the box.
Caution: If you place the library upright with the Y-tray
restraint thumbscrews installed, you could damage
the chassis or the Y-tray.