Quantum Scalar 100 Guía de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 126
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
Installing and Removing Hardware 4-17
Scalar 100
Installing and Removing Hardware
Additional hardware is available that allows you to configure the library to meet your specific needs.
The available hardware includes the following:
Rackmounting hardware (Rackmount Kit)
Side Panels (Floor Model Kit)
Casters (Floor Models only)
Additional Drives
Secondary Power Supply
A Bulk Load Mailbox
Additional Storage Columns (each column can hold up to three magazines)
Storage Networking Controller (SNC)
For information on the SNC, see the SNC 5101 for the Scalar 100 User Manual on the
product CD or available at
www.adic.com.
Rackmounting your Library
If you are rackmounting your library, use the Rackmounting Kit that is available from ADIC. The
Scalar 100 requires 14U space in a standard 19 inch rack.
Before rackmounting your library, read the following guidelines:
For continued safe operation, the recommended maximum internal ambient temperature of
the rack should not exceed 40
° C.
During installation of a rackmounted unit, do not block or otherwise restrict airflow to the
power supply front or rear vents.
To maintain rack stability, make certain mechanical loading of the rack results in a low
center of gravity.
Before installing a unit into a rack, consider the overall loading of the branch circuit
supplying power to the rack. See
Specifications on page 13-103 for the library power
requirements.
Because this unit is intended to be attached to an earth ground, ensure that a reliable path
to earth ground is maintained within the rack.
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 125 126

Comentarios a estos manuales

Sin comentarios