Chapter 14 Troubleshooting
Over Temperature Condition
DLT-S4 Product Manual 128
Over Temperature Condition 14
The DLT-S4 tape drive has a thermal sensor located in the tape path. This
sensor, which is used to accurately monitor the air temperature in the
tape path, reacts in the following ways:
TapeAlert occurs at 50 °C
Shutdown occurs at 53 °C
SCSI status indicates the tape drive is in the over temperature condition.
For more information, see the DLT-S4 Product Specification (81-81279-xx)
and the DLT-S4 Interface Reference Guide (81-81281-xx).
Location
When the tape path temperature sensor
detects an over temperature condition
resulting in shutdown...
Not mounted in a
library
The media rewinds, unloads, and ejects from the
tape drive.
Mounted in a
library
The cartridge rewinds to BOT and unbuckles in
preparation for unloading, but does not
automatically eject.