20 Gathering Systems Assurance Information
Rack Dimensions
The rack must be 19 inches wide and at least 30 inches deep. The rack must accommodate rail mounting
lengths between 24 inches and 34 inches.
Rack Mounting Holes
Additionally, the rack must have one of these types of mounting holes:
Square, unthreaded mounting holes
Round, unthreaded mounting holes
Threaded mounting holes for use with 10-32 hardware
Threaded mounting holes for use with M5 hardware
Rack Space Requirements
Each Pathlight VX configuration has different rack space requirements needed to install the components.
For the Pathlight VX-450, the rack height can vary, however, the rack must provide 8 contiguous
rack units of space for the 4.2 TB Pathlight VX-450.
For the Pathlight VX-650, the rack must be 40 rack units high. The vertical requirements of the
Pathlight VX vary from 30 contiguous rack units in the smallest configuration (3.8 TB Entry-Level
Configuration) to 56 rack units in the largest system (71.6 TB High-Performance Configuration).
Several rack space requirements apply to all Pathlight VX configurations.
rack depth - 30 inches minimum
rack width - 19 inches
component
rail mounting length - 24 inches to 34 inches