Appendix A: Specifications
Environmental Specifications
Quantum Scalar i40 and Scalar i80 User’s Guide 271
Environmental Specifications
The environmental specifications of the library are listed below.
Note: Temperature ranges apply to product inlet temperatures, not
necessarily to ambient room temperatures. Airflow restrictions
or other heat-generating equipment within the rack enclosure
may cause a rise over ambient room temperatures.
Air Clearance Requirements
There must be at least 4 in. (10 cm) of open space in front of and behind
the library for proper air flow
Operating Non-Operating Shipping and Storage
Altitude –500 to 10,000 ft
(–152 to 3,048 m)
–500 to 10,000 ft
(–152 to 3,048 m)
–500 to 10,000 ft
(–152 to 3,048 m)
Te m pe ra t ur e 50º to 95º F
(10º to 35º C)
50º to 113º F
(10º to 45º C)
–40º to 140º F
(–40º to 60º C)
Relative Humidity 20 to 80%,
non-condensing
10 to 90%,
non-condensing
0 to 95%,
non-condensing